CVE-2019-13940
- State
- Published
- Severity
- 5.3 Medium
- Published
- Feb 11, 2020
- Updated
- Aug 5, 2024
- Reserved
- Jul 18, 2019
Description
A vulnerability has been identified in SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.X.17), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.X.17), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.1), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.X.17), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.X.17), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX 2010 (All versions), SIMATIC WinAC RTX F 2010 (All versions), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.X.17), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.X.17), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.X.17), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.X.17). Affected devices contain a vulnerability that could cause a denial of service condition of the web server by sending specially crafted HTTP requests to ports 80/tcp and 443/tcp.
Beyond the web service, no other functions or interfaces are affected by the denial of service condition.
Scores
| CVSS | Score | Vector | Source |
|---|---|---|---|
| 3.1 | 5.3 Medium | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L/E:P/RL:O/RC:C | siemens |
Weaknesses
- CWE-400 Uncontrolled Resource Consumption
Affected Products
| Product | Versions |
|---|---|
SIMATIC ET 200pro IM154-8 PN/DP CPUSiemens |
|
SIMATIC ET 200pro IM154-8F PN/DP CPUSiemens |
|
SIMATIC ET 200pro IM154-8FX PN/DP CPUSiemens |
|
SIMATIC ET 200S IM151-8 PN/DP CPUSiemens |
|
SIMATIC ET 200S IM151-8F PN/DP CPUSiemens |
|
SIMATIC S7-1200 CPU family (incl. SIPLUS variants)Siemens |
|
SIMATIC S7-300 CPU 314C-2 PN/DPSiemens |
|
SIMATIC S7-300 CPU 315-2 PN/DPSiemens |
|
SIMATIC S7-300 CPU 315F-2 PN/DPSiemens |
|
SIMATIC S7-300 CPU 315T-3 PN/DPSiemens |
|
SIMATIC S7-300 CPU 317-2 PN/DPSiemens |
|
SIMATIC S7-300 CPU 317F-2 PN/DPSiemens |
|
SIMATIC S7-300 CPU 317T-3 PN/DPSiemens |
|
SIMATIC S7-300 CPU 317TF-3 PN/DPSiemens |
|
SIMATIC S7-300 CPU 319-3 PN/DPSiemens |
|
SIMATIC S7-300 CPU 319F-3 PN/DPSiemens |
|
SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)Siemens |
|
SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants)Siemens |
|
SIMATIC WinAC RTX 2010Siemens |
|
SIMATIC WinAC RTX F 2010Siemens |
|
SIPLUS ET 200S IM151-8 PN/DP CPUSiemens |
|
SIPLUS ET 200S IM151-8F PN/DP CPUSiemens |
|
SIPLUS S7-300 CPU 314C-2 PN/DPSiemens |
|
SIPLUS S7-300 CPU 315-2 PN/DPSiemens |
|
SIPLUS S7-300 CPU 315F-2 PN/DPSiemens |
|
SIPLUS S7-300 CPU 317-2 PN/DPSiemens |
|
SIPLUS S7-300 CPU 317F-2 PN/DPSiemens |
|
References