CVE-2020-11639

Insufficient access control on Inter process communication,

State
Published
Severity
7.8 High
Published
Jul 23, 2024
Updated
Aug 4, 2024
Reserved
Apr 8, 2020

Read the record on cve.org

Description

An attacker could exploit the vulnerability by injecting garbage data or specially crafted data. Depending on the data injected each process might be affected differently. The process could crash or cause communication issues on the affected node, effectively causing a denial-of-service attack. The attacker could tamper with the data transmitted, causing the product to store wrong information or act on wrong data or display wrong information.

This issue affects Advant MOD 300 AdvaBuild: from 3.0 through 3.7 SP2.

For an attack to be successful, the attacker must have local access to a node in the system and be able to start a specially crafted application that disrupts the communication. An attacker who successfully exploited the vulnerability would be able to manipulate the data in such way as allowing reads and writes to the controllers or cause Windows processes in 800xA for MOD 300 and AdvaBuild to crash.

Scores

CVSSScoreVectorSource
3.17.8 HighCVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:HABB

Weaknesses

  • CWE-924 Improper Enforcement of Message Integrity During Transmission in a Communication Channel

Affected Products

ProductVersions
Advant MOD 300 AdvaBuildABB
  • 3.0 through 3.7 SP2Affected

References

Every record here comes from the CVE Program’s CVE List. © 1999–2026 The MITRE Corporation. CVE is a registered trademark of The MITRE Corporation. The records are reproduced under the CVE Program terms of use.