CVE-2020-28388
- State
- Published
- Severity
- 6.5 Medium
- Published
- Feb 9, 2021
- Updated
- Jun 2, 2026
- Reserved
- Nov 10, 2020
Description
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.
Scores
| CVSS | Score | Vector | Source |
|---|---|---|---|
| 3.1 | 6.5 Medium | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L/E:P/RL:O/RC:C | siemens |
Weaknesses
- CWE-342 Predictable Exact Value from Previous Values
Affected Products
| Product | Versions |
|---|---|
APOGEE PXC Compact (BACnet)Siemens |
|
APOGEE PXC Compact (P2 Ethernet)Siemens |
|
APOGEE PXC Modular (BACnet)Siemens |
|
APOGEE PXC Modular (P2 Ethernet)Siemens |
|
Nucleus NETSiemens |
|
Nucleus ReadyStart V3Siemens |
|
Nucleus Source CodeSiemens |
|
PLUSCONTROL 1st GenSiemens |
|
TALON TC Compact (BACnet)Siemens |
|
TALON TC Modular (BACnet)Siemens |
|
References