CVE-2022-2502
- State
- Published
- Severity
- 7.5 High
- Published
- Jul 26, 2023
- Updated
- Mar 5, 2025
- Reserved
- Jul 21, 2022
Description
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Scores
| CVSS | Score | Vector | Source |
|---|---|---|---|
| 3.1 | 7.5 High | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H | Hitachi Energy |
Weaknesses
- CWE-20 Improper Input Validation
Affected Products
| Product | Versions |
|---|---|
RTU500 seriesHitachi Energy |
|
References
Every record here comes from the CVE Program’s CVE List. © 1999–2026 The MITRE Corporation. CVE is a registered trademark of The MITRE Corporation. The records are reproduced under the CVE Program terms of use.