CVE-2022-4608

State
Published
Severity
7.5 High
Published
Jul 26, 2023
Updated
Mar 5, 2025
Reserved
Dec 19, 2022

Read the record on cve.org

Description

A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.

Scores

CVSSScoreVectorSource
3.17.5 HighCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HHitachi Energy

Weaknesses

Affected Products

ProductVersions
RTU500 seriesHitachi Energy
  • RTU500 series CMU Firmware version 13.3.1Affected
  • RTU500 series CMU Firmware version 13.3.2Affected
  • RTU500 series CMU Firmware version 13.3.3Not affected
  • RTU500 series CMU Firmware version 13.4.1Not affected

References

Every record here comes from the CVE Program’s CVE List. © 1999–2026 The MITRE Corporation. CVE is a registered trademark of The MITRE Corporation. The records are reproduced under the CVE Program terms of use.