CVE-2023-2071

FactoryTalk View Machine Edition Vulnerable to Remote Code Execution

State
Published
Severity
9.8 Critical
Published
Sep 12, 2023
Updated
Sep 25, 2024
Reserved
Apr 14, 2023

Read the record on cve.org

Description

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

Scores

CVSSScoreVectorSource
3.19.8 CriticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HRockwell

Weaknesses

  • CWE-20 Improper Input Validation

Affected Products

ProductVersions
FaRockwell Automation
  • <=13.0Affected

References

Every record here comes from the CVE Program’s CVE List. © 1999–2026 The MITRE Corporation. CVE is a registered trademark of The MITRE Corporation. The records are reproduced under the CVE Program terms of use.