CVE-2025-7693
Rockwell Automation Micro800 Vulnerability
- State
- Published
- Severity
- 9.3 Critical
- Published
- Aug 18, 2025
- Updated
- Aug 18, 2025
- Reserved
- Jul 15, 2025
Description
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
Scores
| CVSS | Score | Vector | Source |
|---|---|---|---|
| 4.0 | 9.3 Critical | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N | Rockwell |
Weaknesses
- CWE-20 Improper Input Validation
Affected Products
| Product | Versions |
|---|---|
PLC - Micro850 L50ERockwell Automation |
|
References