CVE-2025-9041

Rockwell Automation FLEX 5000 I/O - Module Fault

State
Published
Severity
8.7 High
Published
Aug 14, 2025
Updated
Aug 14, 2025
Reserved
Aug 14, 2025

Read the record on cve.org

Description

A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.

Scores

CVSSScoreVectorSource
4.08.7 HighCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:NRockwell

Weaknesses

  • CWE-1287 Improper Validation of Specified Type of Input

Affected Products

ProductVersions
FLEX 5000 I/ORockwell Automation
  • Version 2.011 or belowAffected

References

Every record here comes from the CVE Program’s CVE List. © 1999–2026 The MITRE Corporation. CVE is a registered trademark of The MITRE Corporation. The records are reproduced under the CVE Program terms of use.