CVE-2026-115794
Alarm data length not validated against received frame length
- State
- Published
- Severity
- 2.3 Low
- Published
- Oct 29, 2026
- Updated
- Oct 29, 2026
- Reserved
- Oct 23, 2026
Description
P-Net before 1.0.3 passes the application alarm callback a data length derived from the variable part length field of a received RTA alarm frame without checking it against the length of the received frame. A short frame can make the callback receive a length of up to 65507 bytes. An application that copies the reported number of bytes reads past the end of the receive buffer. The attacker must have established an Application Relationship and requires ADJACENT network access. Applications that do not use the alarm data are not affected.
Scores
| CVSS | Score | Vector | Source |
|---|---|---|---|
| 4.0 | 2.3 Low | CVSS:4.0/AV:A/AC:L/AT:P/PR:N/UI:N/VC:L/VI:N/VA:L/SC:N/SI:N/SA:N | rt-labs |
Weaknesses
- CWE-130 Improper Handling of Length Parameter Inconsistency
Affected Products
| Product | Versions |
|---|---|
P-NetRT-Labs |
|
References
Every record here comes from the CVE Program’s CVE List. © 1999–2026 The MITRE Corporation. CVE is a registered trademark of The MITRE Corporation. The records are reproduced under the CVE Program terms of use.