CVE-2026-15203
Debug interfaces are accessible by default in Danfoss iC7 Automation SP, iC7 Marine and iC7 7Hybrid software
- State
- Published
- Severity
- 9.3 Critical
- Published
- Aug 26, 2026
- Updated
- Aug 26, 2026
- Reserved
- Jul 9, 2026
Description
Improper access control in debug and engineering interfaces in Danfoss iC7-Automation SP, iC7-Marine, and iC7-Hybrid GR3 allows attackers to gain read/write access to internal values, upload and execute unsigned applications, and upload unsigned EEPROM data and firmware via exposed service interfaces and software update mechanisms
Scores
| CVSS | Score | Vector | Source |
|---|---|---|---|
| 4.0 | 9.3 Critical | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:L | Danfoss |
Weaknesses
- CWE-1191 On-Chip debug and test interface with improper access control
Affected Products
| Product | Versions |
|---|---|
iC7-Automation SPDanfoss |
|
iC7-MarineDanfoss |
|
iC7-HybridDanfoss |
|