CVE-2026-16316
Malformed IEC 61850 Sampled Values frames cause partial denial of service in StationGuard
- State
- Published
- Severity
- 1.3 Low
- Published
- Aug 6, 2026
- Updated
- Aug 6, 2026
- Reserved
- Jul 20, 2026
Description
OMICRON StationGuard 4.00 contains an improper input validation vulnerability in its IEC 61850 Sampled Values (SV) frame processing. A specially crafted SV frame can cause the affected process to terminate, disrupting alert processing for Sampled Values traffic. The vulnerability does not affect overall system availability or the processing of other traffic types, and the process is automatically restarted, and the failure is immediately reported to the user.
Scores
| CVSS | Score | Vector | Source |
|---|---|---|---|
| 4.0 | 1.3 Low | CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N/E:U/R:A/RE:M | OMICRON |
| 3.1 | 4.3 Medium | CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L | OMICRON |
Weaknesses
- CWE-20 Improper input validation
Affected Products
| Product | Versions |
|---|---|
OMICRON StationGuardOMICRON electronics GmbH |
|
References
- https://www.omicronenergy.com/.well-known/csaf/osa-21.jsonvendor-advisory
Every record here comes from the CVE Program’s CVE List. © 1999–2026 The MITRE Corporation. CVE is a registered trademark of The MITRE Corporation. The records are reproduced under the CVE Program terms of use.