CVE-2026-3611
Honeywell IQ4x BMS Controller Missing authentication for critical function
- State
- Published
- Severity
- 10.0 Critical
- Published
- Mar 12, 2026
- Updated
- Mar 30, 2026
- Reserved
- Mar 5, 2026
Description
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Scores
| CVSS | Score | Vector | Source |
|---|---|---|---|
| 4.0 | 10.0 Critical | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H | icscert |
| 3.1 | 10.0 Critical | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H | icscert |
Weaknesses
- CWE-306 Missing authentication for critical function
Affected Products
| Product | Versions |
|---|---|
IQ4EHoneywell |
|
IQ412Honeywell |
|
IQ422Honeywell |
|
IQ4NCHoneywell |
|
IQ41xHoneywell |
|
IQ3Honeywell |
|
IQECOHoneywell |
|
References
Every record here comes from the CVE Program’s CVE List. © 1999–2026 The MITRE Corporation. CVE is a registered trademark of The MITRE Corporation. The records are reproduced under the CVE Program terms of use.